ABB Relion RES670 manuals
Relion RES670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- section 1 introduction
- Product documentation
- Document revision history
- Related documents
- Document conventions
- IEC61850 edition 1 / edition 2 mapping
- safety information
- Caution signs
- Note signs
- Section 3 Available functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 4 Starting up
- Checking the power supply
- IED start-up sequence
- Writing an application configuration to the IED
- Checking CT circuits
- Checking VT circuits
- Checking the binary I/O circuits
- Binary output circuits
- Section 5 Configuring the IED and changing settings
- Configuring analog CT inputs
- Section 6 Establishing connection and verifying the SPA/IEC communication
- Verifying the communication
- Fibre optic loop
- Section 7 Establishing connection and verifying the LON communication
- The LON Protocol
- Optical budget calculation for serial communication with LON
- Section 8 Establishing connection and verifying the IEC
- Section 9 Establishing connection and verifying the IEEE C37.118/1344 communication
- Setting the PMU station communication (PMU configuration)
- Setting the TCP/UDP client communication
- Verifying the IEEE C37.118/1344 TCP communication
- Verifying the IEEE C37.118/1344 UDP communication
- Optical budget calculation for RES670 - PDC communication
- Preparing for test
- Preparing the IED to verify settings
- Activating the test mode
- Connecting the test equipment to the IED
- Releasing the function to be tested
- Verifying analog primary and secondary measurement
- Testing the protection functionality
- Forcing of binary I/O signals for testing
- Enable forcing using TESTMODE function block
- Forcing by using PCM600
- How to undo forcing changes and return the IED to normal operation
- Undo forcing by using PCM600
- Testing disturbance report
- Event recorder (ER) and Event list (EL)
- Identifying the function to test in the technical reference manual
- Verifying the settings
- Testing the power swing detection function ZMRPSB (68)
- or FRPSPDIS (21) and ZMRPSB (78)
- Current protection
- Completing the test
- Four step non-directional ground fault protection
- Measuring the trip and time limit for set values
- Two step overvoltage protection OV2PTOV (59)
- Built-in overcurrent feature (non-directional)
- Overcurrent feature with current restraint
- Over/Undervoltage feature
- Measuring the trip value for the negative sequence function
- Measuring the trip value for the zero-sequence function
- Checking the operation of the dv/dt and di/dt based function
- Logic
- ph/2ph/3ph operating mode
- Circuit breaker lockout
- Metering
- Station communication
- clearing system
- Visual inspection
- Preparation
- Self supervision check
- Restoring
- troubleshooting
- Communication Diagnostics
- Fault tracing
- Using front-connected PC
- Repair instruction
- Repair support
- Section 14 Glossary
Relion RES670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Related documents
- Document symbols and conventions
- Section 2 Safety information
- Caution signs
- Note signs
- Section 3 Environmental aspects
- Section 4 Unpacking, inspecting and storing
- Returning an IED damaged in transit
- Section 5 Mounting
- Flush mounting
- Mounting procedure for flush mounting
- panel rack mounting
- Mounting procedure for 19" panel rack mounting
- Wall mounting
- Mounting procedure for wall mounting
- Side-by-side 19" rack mounting
- Mounting procedure for side-by-side rack mounting
- Side-by-side flush mounting
- Mounting procedure for side-by-side flush mounting
- Mounting the coupling capacitor unit REX061 and shunt resistor unit REX062 (REG670 only)
- Shunt resistor unit REX062
- Making the electrical connection
- Front side connectors
- Rear side connectors
- Connection examples for high impedance differential protection
- Connecting to protective earth
- Connecting the power supply module
- Connecting the binary input and output signals
- Making the shield connection
- Making the electrical connection to the rotor and stator injection equipment (REG670 only)
- Coupling capacitor unit REX061
- Connecting injection unit REX060, coupling capacitor unit REX061 and shunt resistor unit REX062
- Connecting and setting voltage inputs
- Making of Ethernet connections
- Connecting remote communication interfaces LDCM
- Installing the serial communication cable for RS485
- Installing the serial communication cable for RS485 SPA/IEC
- Data on RS485 serial communication module cable
- Electrical installation
- Section 7 Checking installation
- Section 8 Removing, repairing and exchanging
- Sending the IED for repair
- Section 9 Technical data
- Case with rear cover
- Flush mounting dimensions
- Side-by-side flush mounting dimensions
- Wall mounting dimensions
- Section 10 Glossary
Relion RES670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Document symbols and conventions
- Document conventions
- Section 2 Application
- Wide area measurement functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 3 Configuration
- Description of configuration B20
- Section 4 Analog inputs
- Example
- Example 2
- Examples on how to connect, configure and set CT inputs for most commonly used CT connections
- Example on how to connect a wye connected three-phase CT set to the IED
- Example how to connect delta connected three-phase CT set to the IED
- Example how to connect single-phase CT to the IED
- Relationships between setting parameter Base Current, CT rated primary current and minimum pickup of a protection IED
- Examples how to connect, configure and set VT inputs for most commonly used VT connections
- Example on how to connect a phase-to-phase connected VT to the IED
- Example on how to connect an open delta VT to the IED for high impedance grounded or ungrounded netwoeks
- Example how to connect the open delta VT to the IED for low impedance grounded or solidly grounded power systems
- Example on how to connect a neutral point VT to the IED
- Section 5 Local HMI
- Display
- LEDs
- Keypad
- Local HMI functionality
- Parameter management
- Section 6 Wide area measurement system
- Operation principle
- Frequency reporting
- Reporting filters
- Scaling Factors for ANALOGREPORT channels
- PMU Report Function Blocks Connection Rules in PCM600 Application Configuration Tool (ACT)
- Setting guidelines
- Section 7 Impedance protection
- Basic characteristics
- Out-of-step protection OOSPPAM (78)
- Section 8 Current protection
- Settings for each step
- Four step residual overcurrent protection, (Zero sequence or negative sequence directionality) EF4PTOC (51N/67N)
- Common settings for all steps
- nd harmonic restrain
- Parallel transformer inrush current logic
- Four step directional negative phase sequence overcurrent protection NS4PTOC (46I2)
- Sensitive directional residual overcurrent and power protection SDEPSDE (67N)
- LCPTTR (26)
- Identification
- Directional underpower protection GUPPDUP (37)
- Directional overpower protection GOPPDOP (32)
- Section 9 Voltage protection
- Two step overvoltage protection OV2PTOV (59)
- Equipment protection, capacitors
- Section 10 Frequency protection
- Overfrequency protection SAPTOF (81)
- Frequency time accumulation protection function FTAQFVR (81A)
- Section 11 Multipurpose protection
- Current and voltage selection for CVGAPC function
- Base quantities for CVGAPC function
- Application possibilities
- Negative sequence overcurrent protection
- Generator stator overload protection in accordance with IEC or ANSI standards
- Open phase protection for transformer, lines or generators and circuit breaker head flashover protection for generators
- Loss of excitation protection for a generator
- Section 12 System protection and control
- Section 13 Secondary system supervision
- Fuse failure supervision FUFSPVC
- Negative sequence based
- Delta V and delta I
- Section 14 Control
- Selector mini switch VSGAPC
- AutomationBits, command function for DNP3.0 AUTOBITS
- Application
- Tripping logic SMPPTRC (94)
- Three-pole tripping
- Single-, two- or three-pole tripping
- Trip matrix logic TMAGAPC
- Logic for group alarm WRNCALH
- Configurable logic blocks
- Fixed signal function block FXDSIGN
- Boolean 16 to Integer conversion B16I
- Boolean to integer conversion with logical node representation, 16 bit BTIGAPC
- Integer to Boolean 16 conversion IB16
- Integer to Boolean 16 conversion with logic node representation ITBGAPC
- Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
- Comparator for real inputs - REALCOMP
- Setting example
- Measurement
- Zero clamping
- Setting examples
- Gas medium supervision SSIMG (63)
- Breaker monitoring SSCBR
- Event function EVENT
- Disturbance report DRPRDRE
- Recording times
- Analog input signals
- Consideration
- Pulse-counter logic PCFCNT
- Function for energy calculation and demand handling ETPMMTR
- Section 18 Station communication
- Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV
- IEC 61850-8-1 redundant station bus communication
- IEC 61850-9-2LE communication protocol
- Setting examples for IEC 61850-9-2LE and time synchronization
- LON communication protocol
- MULTICMDRCV and MULTICMDSND
- IEC 60870-5-103 communication protocol
- general settings
- DNP3 Communication protocol
- Section 19 Remote communication
- Section 20 Security
- Change lock CHNGLCK
- Denial of service DOS
- IED identifiers
- Measured value expander block RANGE_XP
- Signal matrix for binary outputs SMBO
- Frequency values
- Test mode functionality TEST
- IEC 61850 protocol test mode
- Process bus IEC 61850-9-2LE synchronization
- Section 22 Requirements
- Conditions
- General current transformer requirements
- Current transformers according to IEC 61869-2, class P, PR
- Voltage transformer requirements
- Sample specification of communication requirements for the protection and control terminals in digital telecommunication networks
- IEC 61850-9-2LE Merging unit requirements
- Section 23 Glossary
Relion RES670
Table of contents
- Table Of Contents
- Application
- Available functions
- Differential protection
- Wide area measurement system
- Voltage protection
- Frequency protection
- Secondary system supervision
- Logic
- Monitoring
- Metering
- Basic IED functions
- Remote communication
- Connection diagrams
- Technical data
- electrical safety
- Ordering for customized IED
- Ordering for pre-configured IED
- Ordering for Accessories
Relion RES670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Document symbols and conventions
- Document conventions
- Section 2 Safety information
- Caution signs
- Note signs
- Section 3 Environmental aspects
- Section 4 Unpacking, inspecting and storing
- Storing
- Section 5 Mounting
- Flush mounting
- Mounting procedure for flush mounting
- Mounting procedure for 19" panel rack mounting
- Wall mounting
- Side-by-side 19" rack mounting
- Mounting procedure for side-by-side rack mounting
- Side-by-side flush mounting
- Mounting procedure for side-by-side flush mounting
- Coupling capacitor unit REX061
- Shunt resistor unit REX062
- Section 6 Connecting
- Front side connectors
- Rear side connectors
- Connection examples for high impedance differential protection
- Connecting to protective ground
- Connecting to CT and VT circuits
- Connecting the binary input and output signals
- Making the shield connection
- Making the electrical connection to the rotor and stator injection equipment (REG670 only)
- Connecting injection unit REX060, coupling capacitor unit REX061 and shunt resistor unit REX062
- Connecting and setting voltage inputs
- Making of Ethernet connections
- Connecting remote communication interfaces LDCM
- Installing the serial communication cable for RS485
- Installing the serial communication cable for RS485 SPA/IEC
- Data on RS485 serial communication module cable
- Installing the GPS antenna
- Electrical installation
- Section 7 Checking installation
- Section 8 Removing, repairing and exchanging
- Exchanging the IED
- Section 9 Technical data
- Case with protective cover
- Flush mounting dimensions
- Side-by-side flush mounting dimensions
- Wall mounting dimensions
- Section 10 Glossary
Relion RES670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Intended audience
- Product documentation
- Document revision history
- Related documents
- Document conventions
- IEC 61850 edition 1 / edition 2 mapping
- Section 2 Available functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 3 Analog inputs
- Signals
- Settings
- Monitored data
- Operation principle
- Technical data
- Section 4 Binary input and output modules
- Setting parameters for binary input modules
- Local HMI screen behaviour
- Local HMI signals
- Basic part for LED indication module
- LCD part for HMI function keys control module
- Keypad
- Display
- LEDs
- LED configuration alternatives
- Indication LEDs
- Function keys
- C37.118 Phasor Measurement Data Streaming Protocol Configuration PMUCONF
- IEEE C37.118 Message Framework
- Short guidance for use of TCP
- Short guidance for use of UDP
- Protocol reporting via IEEE 1344 and C37.118 PMUREPORT
- Function block
- Frequency reporting
- Reporting filters
- Scaling Factors for ANALOGREPORT channels
- Power swing detection ZMRPSB (68)
- Resistive reach in forward direction
- Resistive reach in reverse direction
- Basic detection logic
- Operating and inhibit conditions
- Lens characteristic
- Detecting an out-of-step condition
- Maximum slip frequency
- Taking care of the circuit breaker
- Design
- Directional phase overcurrent protection, four steps OC4PTOC(51_67)
- Identification
- Operating quantity within the function
- Internal polarizing
- External polarizing for ground-fault function
- Internal ground-fault protection structure
- Directional supervision element with integrated directional comparison function
- Second harmonic blocking element
- Switch on to fault feature
- Four step directional negative phase sequence overcurrent protection NS4PTOC (46I2)
- Internal polarizing facility of the function
- External polarizing for negative sequence function
- Sensitive directional residual overcurrent and power protection SDEPSDE (67N)
- Functionality
- Thermal overload protection, one time constant Fahrenheit Celsius LFPTTR/LCPTTR (26)
- Low pass filtering
- Two step undervoltage protection UV2PTUV (27)
- Time delay
- Blocking
- Functionality OV2PTOV
- Measurement principle
- Underfrequency protection SAPTUF (81)
- Voltage dependent time delay
- Overfrequency protection SAPTOF (81)
- General current and voltage protection CVGAPC
- Base quantities for CVGAPC function
- Built-in undercurrent protection steps
- Built-in overvoltage protection steps
- Multipurpose filter SMAIHPAC
- Filter calculation example
- Current circuit supervision (87)
- Delta current and delta voltage detection
- Dead line detection
- Main logic
- Logic rotating switch for function selection and LHMI presentation SLGAPC
- Graphical display
- Selector mini switch VSGAPC
- Generic communication function for Double Point indication DPGAPC
- Single point generic control 8 signals SPC8GAPC
- AutomationBits, command function for DNP3.0 AUTOBITS
- Tripping logic SMPPTRC (94)
- Logic diagram
- General start matrix block SMAGAPC
- Trip matrix logic TMAGAPC
- AND function block AND
- Controllable gate function block GATE
- Inverter function block INV
- Pulse timer function block PULSETIMER
- Settable timer function block TIMERSET
- ANDQT function block
- Pulse timer function block PULSETIMERQT
- Set/Reset function block SRMEMORYQT
- Exclusive OR function block XORQT
- Setting parameters
- Operation accuracy
- Comparator for integer inputs INTCOMP
- Comparator for real inputs REALCOMP
- Measurements
- Measurements CVMMXN
- Phase current measurement CMMXU
- Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU
- Gas medium supervision SSIMG (63)
- Circuit breaker contact travel time
- Circuit breaker status
- Accumulated energy
- Circuit breaker operation cycles
- Circuit breaker operation monitoring
- Circuit breaker gas pressure indication
- Event function EVENT
- Disturbance report DRPRDRE
- Logical signal status report BINSTATREP
- Measured value expander block RANGE_XP
- Limit counter L4UFCNT
- Reporting
- Pulse-counter logic PCFCNT
- Access point
- Access point diagnostics
- Redundant communication
- Merging unit
- Routes
- Communication protocols
- DNP3 protocol
- Communication interfaces and protocols
- GOOSE function block to receive a double point value GOOSEDPRCV
- GOOSE function block to receive an integer value GOOSEINTRCV
- GOOSE function block to receive a measurand value GOOSEMVRCV
- GOOSE function block to receive a single point value GOOSESPRCV
- Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV
- GOOSE binary receive GOOSEBINRCV
- IEC/UCA 61850-9-2LE communication protocol
- LON communication protocol
- communication ports
- IEC 60870-5-103 communication protocol
- Measurands for IEC 60870-5-103 I103MEAS
- Function status auto-recloser for IEC 60870-5-103 I103AR
- Function commands for IEC 60870-5-103 I103CMD
- IED commands for IEC 60870-5-103 I103IEDCMD
- I103POSCMDV
- Communication ports
- Security events on protocols SECALARM
- Binary signal transfer
- Transmission of local analog data via LDCM to remote end function block LDCMTRN called LDCMTransmit
- Authority check ATHCHCK
- Authorization with Central Account Management enabled IED
- Authority management AUTHMAN
- FTP access with password FTPACCS
- Authority status ATHSTAT
- Internal signals
- Supervision of analog inputs
- ChangeLock function CHNGLCK
- Denial of service DOS
- Time synchronization TIMESYNCHGEN
- Real-time clock (RTC) operation
- Synchronization alternatives
- Process bus IEC/UCA 61850-9-2LE synchronization
- Test mode functionality TESTMODE
- IED identifiers TERMINALID
- Product information PRODINF
- Signal matrix for binary inputs SMBI
- Signal matrix for analog inputs SMAI
- Frequency values
- Summation block 3 phase 3PHSUM
- Overview
- Case from the rear side
- Hardware modules
- Numeric module (NUM)
- Power supply module (PSM)
- Local human-machine interface (Local HMI)
- Analog digital conversion module (ADM)
- Binary input module (BIM)
- Binary output modules (BOM)
- Static binary output module (SOM)
- Binary input/output module (IOM)
- mA input module (MIM)
- Galvanic RS485 communication module
- Optical Ethernet module
- GPS time synchronization module (GTM)
- GPS antenna
- Dimensions
- Case without rear cover
- Flush mounting dimensions
- Side-by-side flush mounting dimensions
- Wall mounting dimensions
- Mounting alternatives
- Mounting procedure for flush mounting
- Mounting procedure for 19" panel rack mounting
- Wall mounting
- Mounting procedure for wall mounting
- Side-by-side 19" rack mounting
- Mounting procedure for side-by-side rack mounting
- Side-by-side flush mounting
- Mounting procedure for side-by-side flush mounting
- Connection system
- Type tests according to standard
- Section 24 Labels
- Section 25 Connection diagrams
- Section 26 Inverse time characteristics
- Principle of operation
- Inverse characteristics
- Section 27 Glossary
Relion RES670
Table of contents
Relion RES670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- About the operator's manual
- Intended audience
- Revision notes
- Section 2 Safety information
- Section 3 Overview
- Section 4 Understand the IED local human-machine interface
- Key activated screens
- Introduction
- Local HMI setup
- Change
- Section 5 Understand the HMI tree
- Section 6 Read measured values
- View analog primary values
- Current phasors CMMXU
- Function for energy calculation and demand handling ETPMMTR
- View events
- Identify a disturbance
- View trip values
- System time and synchronization
- TIMESYNCHBIN
- Power system
- Ethernet configuration
- Analog and I/O modules
- Overview
- Change lock
- Monitoring
- Current sequence components CMSQI
- Fault locator LMBRFLO
- Pulse counter logic PCGGIO
- Four step phase overcurrent protection OC4PTOC
- Frequency protection
- General current and voltage protection CVGAPC
- Event counter CNTGGIO
- LogicRSMemory
- Read internal events
- IED test mode
- View binary output values
- Four step directional negative phase sequence overcurrent protection NS4PTOC
- Two step undervoltage protection UV2PTUV
- Commands
- Logical signal status report BINSTATREP
- IEC61850 generic communication I/O functions
- Integer to Boolean 16 conversion IB16FCVB, IB16
- Communication
- Setting groups
- Control screen messages
- Reset guide for IED
- Reset LEDs
- LogOn or logOff
- Internet Protocol ports security guideline
Relion RES670
Table of contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Section 1 Introduction
- Product documentation
- Document revision history
- Related documents
- Document conventions
- IEC 61850 edition 1 / edition 2 mapping
- Section 2 Application
- Wide area measurement functions
- Back-up protection functions
- Control and monitoring functions
- Communication
- Basic IED functions
- Section 3 Configuration
- Description of configuration RES670
- Description of configuration B20
- Section 4 Analog inputs
- Setting of the phase reference channel
- Example 1
- Example 3
- Examples on how to connect, configure and set CT inputs for most commonly used CT connections
- Example on how to connect a star connected three phase CT set to the IED
- Example how to connect single-phase CT to the IED
- Relationships between setting parameter Base Current, CT rated primary current and minimum pickup of a protection IED
- Examples how to connect, configure and set VT inputs for most commonly used VT connections
- Examples on how to connect a three phase-to-earth connected VT to the IED
- Example on how to connect a phase-to-phase connected VT to the IED
- Example on how to connect an open delta VT to the IED for high impedance earthed or unearthed networks
- for low impedance earthed or solidly earthed power systems
- Section 5 Local HMI
- Display
- LEDs
- Keypad
- Local HMI functionality
- Parameter management
- Front communication
- Protocol reporting via IEEE 1344 and C37.118 PMUREPORT
- Operation principle
- Frequency reporting
- Reporting filters
- Scaling Factors for ANALOGREPORT channels
- PMU Report Function Blocks Connection Rules in PCM600 Application Configuration Tool (ACT)
- Setting guidelines
- Power swing detection ZMRPSB
- Basic characteristics
- Out-of-step protection OOSPPAM
- Directional phase overcurrent protection, four steps OC4PTOC
- Settings for each step
- Setting example
- Directional residual overcurrent protection, four steps EF4PTOC
- Common settings for all steps
- nd harmonic restrain
- Parallel transformer inrush current logic
- Settings for each step (x = 1, 2, 3 and 4)
- Four step directional negative phase sequence overcurrent protection NS4PTOC
- Sensitive directional residual overcurrent and power protection SDEPSDE
- Identification
- Thermal overload protection, one time constant, Celsius Fahrenheit LCPTTR/LFPTTR
- Setting guideline
- Directional underpower protection GUPPDUP
- Directional overpower protection GOPPDOP
- Two step undervoltage protection UV2PTUV
- Settings for two step undervoltage protection
- Two step overvoltage protection OV2PTOV
- Application
- Equipment protection, such as for motors, generators reactors and transformers
- Underfrequency protection SAPTUF
- Overfrequency protection SAPTOF
- Rate-of-change of frequency protection SAPFRC
- Frequency time accumulation protection function FTAQFVR
- Section 11 Multipurpose protection
- Current and voltage selection for CVGAPC function
- Base quantities for CVGAPC function
- Inadvertent generator energization
- Negative sequence overcurrent protection
- Generator stator overload protection in accordance with IEC or ANSI standards
- generators and circuit breaker head flashover protection for generators
- Voltage restrained overcurrent protection for generator and step-up transformer
- Loss of excitation protection for a generator
- Section 12 System protection and control
- Section 13 Secondary system supervision
- Fuse failure supervision FUFSPVC
- Negative sequence based
- Zero sequence based
- Dead line detection
- Section 14 Control
- Tripping logic SMPPTRC
- Three-phase tripping
- Single- and/or three-phase tripping
- Single-, two- or three-phase tripping
- Example of directional data
- Blocking of the function block
- Logic for group alarm ALMCALH
- Logic for group indication INDCALH
- Fixed signal function block FXDSIGN
- Boolean 16 to Integer conversion B16I
- Boolean to integer conversion with logical node representation, 16 bit BTIGAPC
- Integer to Boolean 16 conversion IB16
- representation ITBGAPC
- Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
- Comparator for real inputs - REALCOMP
- Measurement
- Zero clamping
- Setting examples
- Gas medium supervision SSIMG
- Liquid medium supervision SSIML
- Breaker monitoring SSCBR
- Event function EVENT
- Disturbance report DRPRDRE
- Recording times
- Binary input signals
- Analog input signals
- Consideration
- Logical signal status report BINSTATREP
- Running hour-meter TEILGAPC
- Pulse-counter logic PCFCNT
- Function for energy calculation and demand handling ETPMMTR
- Access point
- Redundant communication
- Merging unit
- Communication protocols
- Receiving data
- IEC/UCA 61850-9-2LE communication protocol
- Specific settings related to the IEC/UCA 61850-9-2LE communication
- Setting examples for IEC/UCA 61850-9-2LE and time synchronization
- IEC 61850 quality expander QUALEXP
- LON communication protocol
- MULTICMDRCV and MULTICMDSND
- IEC 60870-5-103 communication protocol
- Design
- Settings
- Settings for RS485 and optical serial communication
- Settings from PCM600
- Function and information types
- DNP3 Communication protocol
- Binary signal transfer
- Communication hardware solutions
- Authority status ATHSTAT
- Change lock CHNGLCK
- Denial of service SCHLCCH/RCHLCCH
- IED identifiers TERMINALID
- Factory defined settings
- Frequency values
- Test mode functionality TESTMODE
- Process bus IEC/UCA 61850-9-2LE synchronization
- Current transformer requirements
- Conditions
- Fault current
- General current transformer requirements
- PX, PXR (and old IEC 60044-6, class TPS and old British Standard, class X)
- Voltage transformer requirements
- PTP requirements
- IEC/UCA 61850-9-2LE Merging unit requirements
- Application manual
- Section 24 Glossary
Related products
Relion REC670RelionRelion 670 seriesRELION REX640relion REF615Relion RER615RELION REC650Relion REC615Relion REM615RED670 Relion 670 seriesABB categories
Industrial Equipment
DC Drives
Controller
Relays
Measuring Instruments
Circuit breakers
Battery Charger
Industrial Electrical
Transformer
Switch
manualsdatabase
Your AI-powered manual search engine