5 -10 Application Constants: bThe following settings are made with the application constants (B constants): Operation method selection, DCinjection braking, speed searching, timer functions, dwell functions, DROOP functions, energy saving func-tions, and zero-servo.Operation Mode Selections: b1User constants for operation mode selection are shown in the following table.Con-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terPageV/fV/fwithPGOpenLoopVec-torFluxVec-torb1-01 ReferenceselectionSet the frequency referenceinput method.0: Digital Operator1: Control circuit terminal(analog input)2: MEMOBUS communica-tions3: Option board4: Pulse train input0 to 4 1 No Q Q Q Q 180H4-56-66-786-97b1-02OperationmethodselectionSet the Run Command inputmethod.0: Digital Operator1: Control circuit terminal(sequence input)2: MEMOBUS communica-tions3: Option board0 to 3 1 No Q Q Q Q 181H4-56-156-786-97b1-03StoppingmethodselectionUsed to set the stoppingmethod used when a StopCommand is input.0: Deceleration to stop1: Coast to stop2: DC injection braking stop(Stops faster than coast tostop, no regenerativeoperation.)3: Coast to stop with timer(Run Commands aredisregarded duringdeceleration.)0 to 3 * 0 No Q Q Q Q 182H 4-66-17b1-04Prohibitionof reverseoperation0: Reverse enabled1: Reverse disabled 0 or 1 0 No A A A A 183H 6-65