Individual Functions6-101Data TablesThe data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcastdata.Reference DataThe reference data table is shown below. You can both read and write reference data.Note Write 0 to all unused bits. Also, do not write data to reserved registers.INFOSet the number of data specified using command messages as quantity of specified messages x 2. Handleresponse messages in the same way.Register No. Contents0000H Not used0001HFrequency referenceBit 0 Forward Run/Stop Command 1: Forward run 0: StopBit 1 Reverse Run/Stop Command 1: Reverse run 0: StopBit 2 External fault 1: Error (EFO)Bit 3 Fault reset 1: Reset commandBit 4 ComNetBit 5 ComCtrlBit 6 Multi-function input command 3Bit 7 Multi-function input command 4Bit 8 Multi-function input command 5Bit 9 Multi-function input command 6Bit A Multi-function input command 7Bit B Multi-function input command 8Bit C to F Not used0002H Frequency reference (Set units using constant o1-03)0003H Not used0004H Not used0005H Not used0006H PID target value0007H Analog output 1 setting (-11 V/-1540 to 11 V/1540)0008H Analog output 2 setting (-11 V/-1540 to 11 V/1540)0009HMulti-function contact output settingBit 0 Contact output (Terminal M1-M2) 1: ON 0: OFFBit 1 PHC1(Contact P1-PC) 1: ON 0: OFFBit 2 PHC2(Contact P2-PC) 1: ON 0: OFFBit 3 to 5 Not usedBit 6 Set error contact (terminal MA-MC) output using bit 7. 1: ON 0: OFFBit 7 Error contact (terminal MA-MC) 1: ON 0: OFFBits 8 to F Not used000AH to 000EH Not used000FHReference selection settingsBit 0 Not usedBit 1 Use MEMOBUS 0006H PID target value 1: Enabled 0: DisabledBits 2 to B Not usedC Broadcast data terminal S5 input 1: Enabled 0: DisabledD Broadcast data terminal S6 input 1: Enabled 0: DisabledE Broadcast data terminal S7 input 1: Enabled 0: DisabledF Broadcast data terminal S8 input 1: Enabled 0: Disabled