User Constant Tables5- 45 Terminal Function Constants: HThe following settings are made with the terminal function constants (H constants): Settings for external ter-minal functions.Multi-function Contact Inputs: H1User constants for multi-function contact inputs are shown in the following tables.* The values in parentheses indicate factory settings when initialized in 3-wire sequence.Multi-function Contact Input FunctionsCon-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terPageV/fV/fwithPGOpenLoopVec-torFluxVec-torH1-01Terminal S3functionselectionMulti-function contact input1 0 to 78 24 No A A A A 400H -H1-02Terminal S4functionselectionMulti-function contact input2 0 to768 14 No A A A A 401H -H1-03Terminal S5functionselectionMulti-function contact input3 0 to78 3 (0) * No A A A A 402H -H1-04Terminal S6functionselectionMulti-function contact input4 0 to 78 4 (3) * No A A A A 403H -H1-05Terminal S7functionselectionMulti-function contact input5 0 to 78 6 (4) * No A A A A 404H -H1-06Terminal S8functionselectionMulti-function contact input6 0 to 78 8 (6) * No A A A A 4-5H -Set-tingValueFunctionControl MethodsPageV/fV/fwithPGOpenLoopVec-torFluxVec-tor0 3-wire sequence (Forward/Reverse Run Command) Yes Yes Yes Yes 6-161 Local/Remote selection (ON: Operator, OFF: Constant setting) Yes Yes Yes Yes 6-782 Option/Inverter selection (ON: Option board) Yes Yes Yes Yes 6-856-1633Multi-step speed reference 1When H3-09 is set to 2, this function is combined with the master/auxiliaryspeed switch.Yes Yes Yes Yes 6-104 Multi-step speed reference 2 Yes Yes Yes Yes 6-105 Multi-step speed reference 3 Yes Yes Yes Yes 6-106 Jog frequency command (higher priority than multi-step speed reference) Yes Yes Yes Yes 6-107 Accel/decel time 1 Yes Yes Yes Yes 6-268 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes Yes 6-799 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes 6-79