iiiSafety Precautions Confirmations upon Delivery Installation WiringCAUTION• Never install an Inverter that is damaged or missing components.Doing so can result in injury.CAUTION• Always hold the case when carrying the Inverter.If the Inverter is held by the front cover, the main body of the Inverter may fall, possibly resulting in injury.• Attach the Inverter to a metal or other noncombustible material.Fire can result if the Inverter is attached to a combustible material.• Install a cooling fan or other cooling device when installing more than one Inverter in the sameenclosure so that the temperature of the air entering the Inverters is below 45°C.Overheating can result in fires or other accidents.WARNING• Always turn OFF the input power supply before wiring terminals.Otherwise, an electric shock or fire can occur.• Wiring must be performed by an authorized person qualified in electrical work.Otherwise, an electric shock or fire can occur.• Be sure to ground the ground terminal. (200 V Class: Ground to 100 Ω or less, 400 V Class:Ground to 10 Ω or less)Otherwise, an electric shock or fire can occur.• Always check the operation of any emergency stop circuits after they are wired.Otherwise, there is the possibility of injury. (Wiring is the responsibility of the user.)• Never touch the output terminals directly with your hands or allow the output lines to come into con-tact with the Inverter case. Never short the output circuits.Otherwise, an electric shock or ground short can occur.• If the power supply is turned ON during the FWD (or REV) Run Command is given, the motor willstart automatically.Turn the power supply ON after verifying that the RUN signal is OFF.Failure to observe this warning may result in injury.• When the 3-wire sequence is set, do not make the wiring for the control circuit unless the multi-function input terminal constant is set.Failure to observe this warning may result in injury.CAUTION• Check to be sure that the voltage of the main AC power supply satisfies the rated voltage of theInverter.Injury or fire can occur if the voltage is not correct.• Do not perform voltage withstand tests on the Inverter.Otherwise, semiconductor elements and other devices can be damaged.• Connect braking resistors, Braking Resistor Units, and Braking Units as shown in the I/O wiringexamples.Otherwise, a fire can occur.