Individual Functions6-107 Using the Timer FunctionMulti-function contact input terminals S3 to S8 can be designated as timer function input terminals, and multi-function output terminals M1-M2, P1-PC, and P2-PC can be designated as timer function output terminals. Bysetting the delay time, you can erase chattering from the sensors and switches.• Set one of the constants H1-01 to H1-06 (multi-function contact input terminal S3 to S8) to 18 (timer func-tion input).• Set H2-01 to H2-03 (multi-function output terminals M1-M2, P1-PC, and P2-PC function selection) to 12(timer function output).Related ConstantsSetting ExampleWhen the timer function input ON time is longer than the value set in b4-01, the timer output function isturned ON. When the timer function input OFF time is longer than the value set in b4-02, the timer outputfunction is turned OFF. An example of timer function operation is given in the following diagram.Fig 6.61 Timer Function Operation ExampleCon-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terV/fV/fwithPGOpenLoopVec-torFluxVec-torb4-01Timer func-tion ON-delay timeSets the timer function outputON-delay time (dead band) forthe timer function input, in 1-second units.Enabled when a timer functionis set in H1- or H2-.0.0 to300.0 0.0 s No A A A A 1A3Hb4-02Timer func-tion OFF-delay timeSets the timer function outputOFF-delay time (dead band) forthe timer function input, in 1-second units.Enabled when a timer functionis set in H1- or H2-.0.0 to300.0 0.0 s No A A A A 1A4HTimer function inputTimer function output