User Constant Tables5- 83 Factory Settings that Change with the Inverter Capacity (o2-04)The factory settings of the following user constants will change if the Inverter capacity (o2-04) is changed.200 V Class InvertersCon-stantNumberName Unit Factory Setting- Inverter Capacity kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15o2-04 kVA selection - 0 1 2 3 4 5 6 7 8b8-03 Energy-saving filter timeconstant s 0.50 (Open loop vector control)b8-04 Energy-saving coeffi-cient - 288.20 223.70 169.40 156.80 122.90 94.75 72.69 70.44 63.13C6-01 CT/VT selection - 1 1 1 1 1 1 1 1 10 0 0 0 0 0 0 0 0C6-02Carrier frequency selec-tion (when VT isselected) *1 *4- 6 *2 6 *2 6 *2 6*2 6*2 6 *2 6 *2 6 *2 6 *2-Carrier frequency selec-tion upper limit (whenVT is selected)*1- 6 6 6 6 6 6 6 6 6E2-01(E4-01) Motor rated current A 1.90 3.30 6.20 8.50 14.00 19.60 26.60 39.7 53.0E2-02(E4-02) Motor rated slip Hz 2.90 2.50 2.60 2.90 2.73 1.50 1.30 1.70 1.60E2-03(E4-03) Motor no-load current A 1.20 1.80 2.80 3.00 4.50 5.10 8.00 11.2 15.2E2-05(E4-05)Motor line-to-line resis-tance Ω 9.842 5.156 1.997 1.601 0.771 0.399 0.288 0.230 0.138E2-06(E4-06) Motor leak inductance % 18.2 13.8 18.5 18.4 19.6 18.2 15.5 19.5 17.2E2-10 Motor iron loss fortorque compensation W 14 26 53 77 112 172 262 245 272L2-02 Momentary power lossridethru time s 0.1 0.1 0.2 0.3 0.5 1.0 1.0 1.0 2.0L2-03 Min. baseblock (BB)time s 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9L2-04 Voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3L2-08 Frequency reductiongain at KEB start °C 95 95 95 95 95 95 95 95 95L8-02 Overheat pre-alarm level °C 95 95 95 100 95 95 95 95 90N5-02 Motor acceleration time s 0.178 0.142 0.166 0.145 0.154 0.168 0.175 0.265 0.244