6 -104Broadcast DataThe following table shows the broadcast data. You can also write this data.Note Bit signals not defined in the broadcast operation signals use local node data signals continuously.ENTER CommandWhen writing constants to the Inverter from the PLC using MEMOBUS communications, the constants aretemporarily stored in the constant data area in the Inverter. To enable these constants in the constant data area,use the ENTER command.There are two types of ENTER commands: ENTER commands that enable constant data in RAM, andENTER commands that write data to EEPROM (non-volatile memory) in the Inverter at the same time asenabling data in RAM.The following table shows the ENTER command data. ENTER command data can only be written.The ENTER command is enabled by writing 0 to register number 0900H or 0901H.RegisterAddress Contents0001HOperation signalBit 0 Run Command 1: Operating 0: StoppedBit 1 Reverse operation command 1: Reverse 0: ForwardBits 2 and 3 Not usedBit 4 External fault 1: Error (set using H1-01)Bit 5 Fault reset 1: Reset command (set using H1-02)Bits 6 to B Not usedBit C Multi-function contact input terminal S5 inputBit D Multi-function contact input terminal S6 inputBit E Multi-function contact input terminal S7 inputBit F Multi-function contact input terminal S8 input0002H Frequencyreference 30000/100%Register No. Contents0900H Write constant data to EEPROM0910H Constant data is not written to EEPROM, but refreshed in RAM only.INFOThe maximum number of times you can write to EEPROM using the Inverter is 100 thousand. Do not fre-quently execute ENTER commands (0900H) written to EEPROM.The ENTER command registers are write-only. Consequently, if reading these registers, the register addresswill become invalid (Error code: 02H).