5 -32 Motor Constant Constants: EThe following settings are made with the motor constant constants (E constants): V/f characteristics and motorconstants.V/f Pattern: E1User constants for V/f characteristics are shown in the following table.Con-stantNum-berName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terPageV/fV/fwithPGOpenLoopVec-torFluxVec-torE1-01 Input volt-age settingSet the Inverter input voltage in1 volt.This setting is used as a refer-ence value in protection func-tions.155 to255*1200 V*1 No Q Q Q Q 300H 4-56-121E1-03 V/f patternselection0 to E: Select from the 15preset patterns.F: Custom user-set patterns(Applicable for settingsE1-04 to E1-10.)0 to F F No Q Q No No 302H 6-121E1-04Max.outputfrequencyTo set V/f characteristics in astraight line, set the same valuesfor E1-07 and E1-09. In thiscase, the setting for E1-08 willbe disregarded.Always ensure that the four fre-quencies are set in the followingmanner:E1-04 (FMAX) ≥ E1-06 (FA) >E1-07 (FB) ≥ E1-09 (FMIN)40.0 to400.0*6 60.0Hz*2No Q Q Q Q 303H 6-12240.0 to300.0*5E1-05 Max.voltage0.0 to255.0*1200.0V*1*2No Q Q Q Q 304H 6-122E1-06 Basefrequency0.0 to400.0*6 60.0Hz*2No Q Q Q Q 305H 6-1220.0 to300.0*5E1-07Mid.outputfrequency0.0 to400.0*6 3.0 Hz*2 No A A A No 306H 6-1220.0 to300.0*5E1-08Mid.outputfrequencyvoltage0.0 to255 *115.0 V*1 *2 No A A A No 307H4-184-196-122E1-09Min.outputfrequency0.0 to400.0*6 1.5 Hz*2 No Q Q Q A 308H 6-1220.0 to300.0*5E1-10Min.outputfrequencyvoltage0.0 to255.0*19.0 V*1 *2 No A A A No 309H4-184-196-122Output voltage (V)Frequency (Hz)