2 -10* The wire thickness is set for copper wires at 75°C.F7A4185R/L1, S/L2, T/L3 M16 78.4 to 98 100 to 325(4/0 to 600)150 × 2P(300 × 2P)Power cables,e.g., 600 V vinylpower cablesU/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M16 78.4 to 98 100 to 325(4/0 to 600)125 × 2P(250 × 2P), 1 M16 78.4 to 98 100 to 325(4/0 to 600)325 × 2P(600 × 2P)3 M16 78.4 to 98 100 to 325(4/0 to 600) -M16 78.4 to 98 100 to 325(4/0 to 600)100 × 2P(3/0 × 2P)r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4 0.5 to 5.5(20 to 10)1.25(16)F7A4220R/L1, S/L2, T/L3 M16 78.4 to 98 100 to 325(4/0 to 600)250 × 2P(500 × 2P)U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M16 78.4 to 98 100 to 325(4/0 to 600)200 × 2P(400 × 2P), 1 M16 78.4 to 98 100 to 325(4/0 to 600)125 × 4P(250 × 4P)3 M16 78.4 to 98 100 to 325(4/0 to 600) -M16 78.4to 98 100 to 325(4/0 to 600)125 × 2P(250 × 2P)r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4 0.5 to 5.5(20 to 10)1.25(16)F7A4300R/L1, S/L2, T/L3 M16 78.4 to 98 100 to 325(4/0 to 600)125 × 4P(250 × 4P)R1/L11, S1/L21, T1/L31 M16 78.4 to 98 100 to 325(4/0 to 600)125 × 2P(250 × 2P)U/T1, V/T2, W/T3 M16 78.4 to 98 100 to 325(4/0 to 600)125 × 4P(4/0 × 4P), 1 M16 78.4 to 98 100 to 325(4/0 to 600)200 × 4P(400 × 4P)3 M16 78.4 to 98 100 to 325(4/0 to 600) -M16 78.4 to 98 100 to 325(4/0 to 600)125 × 2P(250 × 2P)r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4 0.5 to 5.5(20 to 10)1.25(16)Table 2.2 400 V Class Wire Sizes (Continued)InverterModelCIMR-Terminal Symbol Termi-nalScrewsTighteningTorque(N•m)PossibleWire Sizesmm 2 (AWG)Recom-mendedWire Sizemm 2(AWG)Wire Type