6 -110* 1. When C6-01=0, the upper limit is 150.0.* 2. When C6-01=1, the upper limit is 400.0.Monitor Functionsb5-12Selection ofPID feed-back com-mand lossdetection0: No detection of loss of PIDfeedback.1: Detection of loss of PIDfeedback.Operation continues duringdetection, with themalfunctioning contact notoperating.2: Detection of loss of PIDfeedback.Coasts to stop duringdetection, and fault contactoperates.0 to 2 0 No A A A A 1B0Hb5-13PID feed-back com-mand lossdetectionlevelSets the PID feedback lossdetection level as a percentunits, with the maximum outputfrequency at 100%.0 to 100 0% No A A A A 1B1Hb5-14PID feed-back com-mand lossdetectiontimeSets the PID feedback lossdetection level in s units.0.0 to25.5 1.0 s No A A A A 1B2Hb5-15PID sleepfunctionoperationlevelSet the PID sleep function startlevel as a frequency.0.0 to400.0 *10.0 Hz No A A A A 1B3H0.0 to300.0 *2b5-16PID sleepoperationdelay timeSet the delay time until the PIDsleep function starts in seconds.0.0 to25.5 0.0 s No A A A A 1B4Hb5-17Accel/deceltime for PIDreferenceSet the accel/decel time for PIDreference in seconds.0.0 to25.50.0 s No A A A A 1B5H0.0 to6000.0H6-01Pulse traininput functionselection0: Frequency reference1: PID feedback value2: PID target value0 to 2 0 No A A A A 42CHCon-stantNumberName DescriptionOutput Signal Level Dur-ing Multi-Function AnalogOutputMin.UnitControl Methods MEMOBUSRegis-terV/fV/fwithPGOpenLoopVec-torFluxVec-torU1-24 PID feed-back valueMonitors the feedback valuewhen PID control is used.The input for the max. fre-quency corresponds to 100%.10 V: Max. frequency(0 to ± 10 V possible)0.01% A A A A 57HU1-36 PID inputvolumePID feedback volumeGiven as maximum frequency/100%10 V: Max. frequency(0 to ± 10 V possible)0.01% A A A A 63HU1-37 PID outputvolumePID control outputGiven as maximum frequency/100%10 V: Max. frequency(0 to ± 10 V possible)0.01% A A A A 64HCon-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terV/fV/fwithPGOpenLoopVec-torFluxVec-tor