9 -2Standard Inverter SpecificationsThe standard Inverter specifications are listed by capacity in the following tables. Specifications by ModelSpecifications are given by model in the following tables.200V Class* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Inverter, be sure that the Inverter'srated current is applicable for the motor's rated current.* 2. The startup torque for a 200 V Class Inverter for 110 kW is 120% (low carrier).* 3. A 3-wire transformer is required on the power supply for 12-phase rectification.Table 9.1 200 V Class InvertersModel Number CIMR-F7A 20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110Max. applicable motor output(kW) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110Rated input current (A) 3.8 4.9 8.4 11.5 18 24 37 52 68 84 94 120 160 198 237 317 381 457Rated output capacity(kVA) 1.2 1.6 2.7 3.7 5.7 8.8 12 17 22 27 32 44 55 69 82 110 130 160Rated output current (A) 3.2 4.1 7.0 9.6 15 23 31 45 58 71 85 115 145 180 215 283 346 415Max. output voltage (V) 3-phase; 200, 208, 220, 230, or 240 VAC(Proportional to input voltage.)Max. output frequency(Hz)CT selected (low carrier, constant torque applications): 150 Hz max.VT selected (high carrier, variable torque applications): 400 Hz max.Rated voltage (V)Rated frequency (Hz) 3-phase, 200/208/220/230/240 VAC, 50/60 HzAllowable voltage fluctua-tion + 10%, - 15%Allowable frequency fluc-tuation ±5%Measuresfor powersupplyharmonicsDC reactor Optional Built in12-phase rec-tification Not possible Possible *3Output ratings300 Hz max.Power supply characteristicsControl characteristics