6 -86Setting PrecautionsTo switch command inputs between the Communications Option Board and the control circuit terminals, setthe following constants.• Set b1-01 (Reference Selection) to 1 (Control circuit terminal [analog input])• Set b1-02 (Operation Method Selection to 1 (Control circuit terminal (sequence inputs])• Set one of the constants H1-01 to H1-06 (multi-function contact input terminal S3 to S8 function selection)to 2 (Option/Inverter selection). Jog Frequency Operation without Forward and Reverse Commands(FJOG/RJOG)The FJOG/RJOG command functions operate the Inverter using jog frequencies by using the terminal ON/OFF operation. When using the FJOG/RJOG commands, there is no need to input the Run Command.To use this function, set one of the constants H1-01 to H1-06 (multi-function contact input terminal S3 to S8function selection) to 12 (FJOG command) or 13 (RJOG command).Related Constants* 1. The upper limit of the setting range depends on the upper limit set in E1-04.* 2. When C6-01 = 1, the upper limit is 400.00.* 3. When C6-01 = 0, the upper limit is 150.00.Multi-Function Contact Inputs (H1-01 to H1-06)Terminal Status Frequency Reference and Run Command SelectionOFFInverter(Can be operated from frequency reference or control circuit terminal from analog input termi-nal.)ON Communications Option Board(Frequency reference and Run Command are enabled from Communications Option Board.)Con-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terV/fV/fwithPGOpenLoopVec-torFluxVec-tord1-17 Jog frequencyreferenceThe frequency reference whenthe jog frequency referenceselection, FJOG command, orRJOG command is ON.0.00 to400.00*1 *36.00 Hz Yes Q Q Q Q 292H0.00 to300.00*1 *2Set-tingValueFunctionControl MethodsV/fV/fwithPGOpenLoopVec-torFluxVec-tor12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes