User Constant Tables5- 85400 V Class InvertersCon-stantNumberName Unit Factory Setting- Inverter Capacity kW 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15o2-04 kVA selection - 20 21 22 23 24 25 26 27 28 29b8-03 Energy-saving filter timeconstant s 0.50 (Open loop vector control)b8-04 Energy-saving coeffi-cient - 576.40 447.40 338.80 313.60 245.80 236.44 189.50 145.38 140.88 126.26C6-01 CT/VT selection - 1 1 1 1 1 1 11 1 1 10 0 0 0 0 0 0 0 0 0C6-02Carrier frequency selec-tion (when VT isselected) *1 *3- 6 *2 6*2 6 *2 6 *2 6 *2 6*2 6 *2 6 *2 6 *2 6 *2-Carrier frequency selec-tion upper limit (whenVT is selected)*1- 6 6 6 6 6 6 6 6 6 6E2-01(E4-01) Motor rated current A 1.00 1.60 3.10 4.20 7.00 7.00 9.80 13.30 19.9 26.5E2-02(E4-02) Motor rated slip Hz 2.90 2.60 2.50 3.00 2.70 2.70 1.50 1.30 1.70 1.60E2-03(E4-03) Motor no-load current A 0.60 0.80 1.40 1.50 2.30 2.30 2.60 4.00 5.6 7.6E2-05(E4-05)Motor line-to-line resis-tance W 38.198 22.459 10.100 6.495 3.333 3.333 1.595 1.152 0.922 0.550E2-06(E4-06) Motor leak inductance % 18.2 14.3 18.3 18.7 19.3 19.3 18.2 15.5 19.6 17.2E2-10 Motor iron loss fortorque compensation W 14 26 53 77 130 130 193 263 385 440L2-02 Momentary power lossridethru time s 0.1 0.1 0.2 0.3 0.5 0.5 0.8 0.8 1.0 2.0L2-03 Min. baseblock (BB)time s 0.1 0.2 0.3 0.4 0.5 0.6 0.6 0.7 0.8 0.9L2-04 Voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3L8-02 Overheat pre-alarm level °C 95 95 95 90 95 95 95 90 95 95N5-02 Motor acceleration time s 0.178 0.142 0.166 0.145 0.154 0.154 0.168 0.175 0.265 0.244