User Constant Tables5- 65* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.* 2. When the control method is changed, the factory setting will change. The V/f control factory setting is given.L8-05Input open-phase pro-tectionselection0: Disabled1: Enabled (Detects if inputcurrent open-phase,power supply voltageimbalance or main circuitelectrostatic capacitordeterioration occurs.)0 or 1 0 No A A A A 4B1H -L8-07Outputopen-phaseprotectionselection0: Disabled1: Enabled (Detects one out-put open-phase.)2: Enabled (Detects morethan one output open-phases)Output open-phase isdetected at less than 5% ofInverter rated current.When applied motor capac-ity is small for Invertercapacity, output open-phasemay be detected inadvert-ently or open-phase may notbe detected. In this case, setto 0.0 to 10 No A A A A 4B3H -0 to 2L8-09Ground pro-tectionselection0: Disabled1: Enabled 0 or 1 1 No A A A A 4B5H -L8-10Cooling fancontrolselectionSet the ON/OFF control forthe cooling fan.0: ON only when Inverter isON1: ON whenever power isON0 or 1 0 No A A A A 4B6H -L8-11Cooling fancontroldelay timeSet the time in seconds todelay turning OFF the cool-ing fan after the cooling fanOFF command is received.0 to300 60 s No A A A A 4B7H -L8-12 AmbienttemperatureSet the ambient temperature.If set to 60 °C, the Inverteroverload protection function(OL2) will start 20 % earlier.45 to60 45 °C No A A A A 4B8H -L8-15OL2 charac-teristicsselection atlow speeds0: OL2 characteristics atlow speeds disabled.1: OL2 characteristics atlow speeds enabled.0 or 1 1 No A A A A 4BBH -L8-18 Soft CLAselection0: Disable (gain = 0)1: Enable 0 or 1 1*2 No A A A A 4BEH -Con-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terPageV/fV/fwithPGOpenLoopVec-torFluxVec-tor