5 -74 U: Monitor ConstantsThe following settings are made with the monitor constants (U constants): Setting constants for monitoring indrive mode. Status Monitor Constants: U1The constants used for monitoring status are listed in the following table.* The unit is set in o1-03 (frequency units of reference setting and monitor).Con-stantNumberName DescriptionOutput Signal Level Dur-ing Multi-Function AnalogOutputMin.UnitControl Methods MEMOBUSRegis-terV/fV/fwithPGOpenLoopVec-torFluxVec-torU1-01 FrequencyreferenceMonitors/sets the fre-quency reference value.*10 V: Max. frequency(0 to ± 10 V possible)0.01Hz A A A A 40HU1-02 Output fre-quencyMonitors the output fre-quency.*10 V: Max. frequency(0 to ± 10 V possible)0.01Hz A A A A 41HU1-03 Output cur-rent Monitors the output current.10 V: Inverter rated outputcurrent(0 to +10 V, absolute valueoutput)0.1A A A A A 42HU1-04 ControlmethodChecks the current controlmethod. (Cannot be output.) - A A A A 43HU1-05 Motor speed Monitors the detected motorspeed.*10 V: Max. frequency(0 to ± 10 V possible) 0.01Hz No A A A 44HU1-06 Output volt-ageMonitors the output voltagereference value in theInverter.10 V: 200 VAC (400 VAC)(0 to +10 V output)0.1V A A A A 45HU1-07 DC busvoltageMonitors the main DC volt-age in the Inverter.10 V: 400 VDC (800 VDC)(0 to +10 V output) 1 V A A A A 46HU1-08 OutputpowerMonitors the output power(internally detected value).10 V: Inverter capacity(max. applicable motorcapacity)(0 to ± 10 V possible)0.1kW A A A A 47HU1-09 Torque ref-erenceMonitor in internal torquereference value for vectorcontrol.10 V: Motor rated torque(0 to ± 10 V possible) 0.1% No No A A 48H