Wiring Control Circuit Terminals2- 29 Control Circuit Terminal ConnectionsConnections to Inverter control circuit terminals are shown in Fig 2.22.Fig 2.22 Control Circuit Terminal ConnectionsInverterCIMR-F7A2022P2PCOpen collector 1Open collector 2Multi-functionopen-collector outputs48 VDC, 50 mAP1Default:Frequencyagree signalDefault: Zero-speedMAMBMCError contact output250 VAC, 10 mA min. 1 A max.30 VDC, 10 mA min. 1 A max.M1M2Multi-function contact output250 VAC, 10 mA min. 1 A max.30 DC, 10 mA min. 1 A max.Default: RunningsignalACMP Pulse train outputDefault: OutputfrequencyS5S8S1S2S3S4Forward Run/StopReverse Run/StopExternal faultFault resetMulti-functioncontact inputDefaultsIGMEMOBUScommunicationsRS-485/422R-R+S-S+TerminatingresistanceFMAMMulti-function analog output 1ACE(G)-10 to 10 V 2 mAAMFM++−−Default: Output current0 to +10 VDefault: Output current0 to +10 V-10 to 10 V 2 mAMulti-function analog output 2Ammeter adjustment20 kΩAmmeter adjustment20 kΩ+24V 8mASC+24VCN5 (NPN setting)S6S7Multi-step speedsetting 2Jog frequencyselectionPP4 to 20 mA0 to 10 VPulse train input RP+VA1A2AC 0VMaster speed pulse trainFrequency setting power+15 V 20 mAMaster speed reference0 to 10 V (20 kΩ)Master speed reference4 to 20 mA (250 Ω)[0 to 10 V (20 kΩ) input]Frequency settingadjustmentFrequencysetter2 kΩExternalfrequencyreferences2 kΩ 213E(G)A30 to 10 VP-V (−15V 20mA)MAMC430 to 32 kHz (3 kΩ)High level: 3.5 to 13.2 Vinput0 to 32 kHz (2.2 kΩ)Multi-step command 1(Main speed switching)Externalbaseblock commandfor Braking UnitThermal switch contactShield wireconnection terminalMulti-function anlog input0 to 10 V (20 kΩ)Factory setting:Not used