Trial Operation Procedures4- 5 Basic SettingsSwitch to the quick programming mode (the QUICK indicator on the Digital Operation should be lit) and thenset the following user constants. Refer to Chapter 3 Digital Operator and Modes for Digital Operator operat-ing procedures and to Chapter 5 User Constants and Chapter 6 Constant Settings by Function for details onthe user constants.Constants that must be set are listed in Table 4.1 and those that are set according to the application are listed inTable 4.2.Table 4.1 Basic Settings of ConstantsConstantNumber Name Description Setting Range FactorySetting PageA1-02 Control methodselectionSet the control method for the Inverter.0: V/f control1: V/f control with PG2: Open-loop vector control0 to 20 5-80 to 3b1-01 Reference selectionSet the frequency reference input method.0: Digital Operator1: Control circuit terminal (analog input)2: MEMOBUS communications3: Option board4: Pulse train input0 to 4 15-106-66-786-97b1-02 Operation methodselectionSet the Run Command input method.0: Digital Operator1: Control circuit terminal (sequence input)2: MEMOBUS communications3: Option board0 to 3 15-106-156-786-97C1-01 Acceleration time 1 Set the acceleration time in seconds for theoutput frequency to climb from 0% to 100%.0.0 to 6000.0 s*1 10.0 s 5-206-25C1-02 Deceleration time 1 Set the deceleration time in seconds for theoutput frequency to fall from 100% to 0%.0.0 to 6000.0 s*1 10.0 s 5-206-25C6-01 CT/VT selectionSet to CT (not low noise, maximum currentoverload: 150%) or VT (low noise, maxi-mum current overload:120%).0: CT1: VT0 or 11*25-256-20*2E1-01 Input voltage set-tingSet the Inverter's nominal input voltage involts.This setting is used as a reference value inprotection functions.155 to 255 V(200 V Class)310 to 510 V(400 V Class)200 V(200 VClass)400 V(400 VClass)5-326-121E2-01 Motor rated current Set the motor rated current.10% to 200% ofInverter's ratedcurrentSetting forgeneral-purposemotor ofsamecapacity asInverter5-346-606-1193: Flux vector control