Run Command6- 15Run CommandThis section explains input methods for the Run Command. Selecting the Run Command SourceSet constant b1-02 to select the source for the Run Command.Related ConstantsPerforming Operations Using a Digital OperatorWhen b1-02 is set to 0, you can perform Inverter operations using the Digital Operator keys (RUN, STOP,JOG, and FWD/REV). For details on the Digital Operator, refer to Chapter 3 Digital Operator and Modes.Performing Operations Using Control Circuit TerminalsWhen b1-02 is set to 1, you can perform Inverter operations using the control circuit terminals.Performing Operations Using a 2-wire SequenceThe factory setting is set to a 2-wire sequence. When control circuit terminal S1 is set to ON, forward opera-tion will be performed, and when S1 is turned OFF, the Inverter will stop. In the same way, when control cir-cuit terminal S2 is set to ON, reverse operation will be performed, and when S2 is turned OFF, the Inverterwill stop.Fig 6.12 2-wire Sequence Wiring ExampleCon-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terV/fV/fwithPGOpenLoopVec-torFluxVec-torb1-02Operationmethod selec-tionSet the Run Command inputmethod.0: Digital Operator1: Control circuit terminal(sequence input)2: MEMOBUS communica-tions3: Option board0 to 3 1 No Q Q Q Q 181HInverterForward/stopReverse/stopSequence common