User Constant Tables5- 73 T: Motor AutotuningThe following settings are made with the motor autotuning constants (T constants): Settings for autotuning.* 1. Set T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 is possible for V/f control or V/f control with PG.* 2. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.* 3. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.* 4. The factory setting depends on the Inverter capacity. The values for a 200 V Class Inverter for 0.4 kW are given.* 5. When C6-01 = 1, the upper limit is 400.00.* 6. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter for 0.4 kW is given.* 7. When C6-01 = 0, the upper limit is 150.0.* 8. When the control method is changed, the factory setting will change. The V/f control factory setting is given.Con-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terPageV/fV/fwithPGOpenLoopVec-torFluxVec-torT1-00 Motor 1/2selectionSet the location where theautotuned motor constantsare to be stored.1: E1 to E2 (motor 1)2: E3 to E4 (motor 2)1 or 2 1 No Yes Yes Yes Yes 700H 4-13T1-01 Autotuningmode selec-tionSet the autotuning mode.0: Rotational autotuning1: Stationary autotuning 12: Stationary autotuning forline-to-line resistanceonly0 to 2*12*8 No Yes Yes Yes Yes 701H 4-104-130 to 2,4 *1T1-02 Motor out-put power Set the output power of themotor in kilowatts. 0.00 to650.000.40kW*4No Yes Yes Yes Yes 702H 4-13T1-03 Motor ratedvoltage Set the rated voltage of themotor in volts.0.0 to255.0*2 200.0 V*2 No No No Yes Yes 703H 4-13T1-04 Motor ratedcurrent Set the rated current of themotor in amps.0.32 to6.40 *3 1.90 A*4 No Yes Yes Yes Yes 704H 4-13T1-05 Motor basefrequency Set the base frequency of themotor in hertz.0.0 to400.0*760.0Hz No No No Yes Yes 705H 4-130.0 to300.0*5T1-06 Number ofmotor poles Set the number of motorpoles. 2 to 48poles 4 poles No No No Yes Yes 706H 4-13T1-07 Motor basespeedSet the base speed of themotor in min-1 .0 to240001750min-1 No No No Yes Yes 707H 4-13T1-08Number ofPG pulseswhen turn-ingSet the number of pulses perrevolution for the PG beingused (pulse generator orencoder) without any multi-plication factor.0 to60000 600 No No No No Yes 708H 4-13T1-09 Motor no-load currentSet the current valuerecorded in the motor’s testresults for a motor without aload.Displayed only when Sta-tionary autotuning 2 isselected (T1-01 = 4).0.00 to1.89 *6 1.20A*4 No No No Yes Yes 709H 4-134: Stationary autotuning 2