6 -78Input Terminal FunctionsThis section explains input terminal functions, which set operating methods by switching functions for themulti-function contact input terminals (S3 to S8). Temporarily Switching Operation between Digital Operator and ControlCircuit TerminalsYou can switch the Inverter Run Command inputs and frequency reference inputs between local (i.e., DigitalOperator) and remote (input method using b1-01 and b1-02).You can switch between local and remote by turning ON and OFF the terminals if an output from H1-01 toH1-06 (multi-function contact input terminal S3 to S8 function selection) has been set to 1 (local/remote selec-tion).To set the control circuit terminals to remote, set b1-01 and b1-02 to 1 (Control circuit terminals).Related ConstantsCon-stantNumberName Description SettingRangeFactorySettingChangeduringOpera-tionControl Methods MEMOBUSRegis-terV/fV/fwithPGOpenLoopVec-torFluxVec-torb1-01 ReferenceselectionSet the frequency referenceinput method.0: Digital Operator1: Control circuit terminal(analog input)2: MEMOBUS communica-tions3: Option board4: Pulse train input0 to 4 1 No Q Q Q Q 180Hb1-02Operationmethod selec-tionSet the Run Command inputmethod.0: Digital Operator1: Control circuit terminal(sequence input)2: MEMOBUS communica-tions3: Option board0 to 3 1 No Q Q Q Q 181HINFOYou can also perform local/remote switching using the LOCAL/REMOTE Key on the Digital Operator. Whenthe local/remote function has been set in the external terminals, the LOCAL/REMOTE Key function on theDigital Operator will be disabled.