7 Product-specific CAN objects XN300 slice modules7.8 XN-322-8DO-P05Gateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu 1317.8 XN-322-8DO-P05This module supports the provision of data for digital outputs as per the spec-ifications in CiA401. It allows for process data to be accessed with variousvendor-specific objects.A distinction is drawn between the following CANopen objects within thiscontext:• System-specific objects that the CANopen standard requires for a sys-tem.• Product-specific objects that the CANopen standard requires for a prod-uct group, e.g., for analog modules.• Vendor-specific objects that the CANopen standard does not require andthat the manufacturer implements for data communication purposes.Figure 59: Block diagram showing the various CANopen objects for digital outputsProduct-specific CANopen objectsManufacturer-specific objectsIndex range for the XN-322-8DO-P05 module: x190 to x19FherstellerspezifischproduktspezifischCANReceptionCANReceptionCANTransmissionSingle DigitalOutputENTRYinto 6200h0 (Error State)Switch ifdeviceFailureLatchedOutputValueRECEIVERPDO1Digital Output1_82190hModule DiagnosticMessage 3190hDeviceDiagnosticIndex(hex)Data Type Name Function Mapping Access0x6200 UNSIGNED8 Q-BYTEWrite Digital Output8-bitDefault rww PDO → Section "7.1.1 Read DigitalInput 8-Bit (Object 0x6000)“