7 Product-specific CAN objects XN300 slice modules7.19 XN-322-4AIO-U2248 Gateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu7.19.15 Analog Input Selection (Object 0x51A0)Object 0x51A0 must be used to configure the channels' measuring method.Design of the data bytes:Byte 0:Byte 1:Feature Description / Value EDSName AnalogInputSelection [MxSubExt51A0ParameterName=AnalogInputSelectionObjectType=0x7DataType=0x0006AccessType=rwPDOMapping=0Count=1Description Analog Input SelectionObject Code ARRAYMapping SDOData type UNSIGNED16Sub index 01 … FE hexAccess rwDefault value 0000 hex1 Byte Byte 0:Sub index1≦n≦254B15B14B13B12B11B10B9B8B7B6B5B4B3B2B1B0MSBLSBData bit Desig-nationDescription0 Channel10 = Differential measurement1 = AI1-grounded measurement1 Channel20 = Differential measurement1 = AI2-grounded measurement2 – 7 reservedData bit Desig-nationDescription8 – 15 reserved