7 Product-specific CAN objects XN300 slice modules7.15 XN-322-7AI-U2PT196 Gateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu7.15.13 Channel Measuring Configuration (Object 0x5080)Object 0x5080 can be used to configure the measuring method for a chan-nel.Data word structure:Word 0:Feature Description / Value EDSName ChannelMeasuringConfig [MxSubExt5080ParameterName=ChannelMeasuringConfigObjectType=0x7DataType=0x0006AccessType=rwDefaultValue=1PDOMapping=0Count=1Description Channel Measuring ConfigurationObject Code ARRAYMapping SDOData type UNSIGNED16Sub index 01 … FE hexAccess rwDefault value 0000 hexWordSub index1≦n≦254B15B14B13B12B11B10B9B8B7B6B5B4B3B2B1B0MSBLSBData bit Designation Description Notes0 Analog Input 1 0 = Analog measurement ± 10V1 = Temperature measurement1 0 = KTY10 Sensor1 = PT1000 Sensor2 0 = Differential measurement1 = AI1- grounded measurement3 Analog Input 2 0 = Differential measurement1 = AI1- grounded measurement4 Analog Input 3 0 = Differential measurement1 = AI1- grounded measurement5 Analog Input 4 0 = Differential measurement1 = AI1- grounded measurement6 Analog Input 5 0 = Differential measurement1 = AI1- grounded measurement7 Analog Input 6 0 = Differential measurement1 = AI1- grounded measurement8 Sensor selection 0: KTY10 Sensor1: Pt1000 Sensor9-15 reserved