7 Product-specific CAN objects XN300 slice modules7.16 XN-322-8AI-IGateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu 2117.16.13 Channel Measuring Configuration (Object 0x5090)Object 0x5090 must be used to configure the channels' measuring method.Design of the data bytes:Byte 0:Byte 1:Feature Description / Value EDSName Channel1MeasuringConfig [MxSubExt5090ParameterName=ChannelMeasuringConfigObjectType=0x7DataType=0x0006AccessType=rwPDOMapping=0Count=1Description Channel Measuring ConfigurationObject Code ARRAYMapping SDOData type UNSIGNED16Sub index 01 … FE hexAccess rwDefault value 0000 hex1 Byte Byte 0:Sub index1≦n≦254B15B14B13B12B11B10B9B8B7B6B5B4B3B2B1B0MSBLSBData bit Designation Description0 Channel 1 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mA1 Channel 2 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mA2 Channel 3 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mA3 Channel 4 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mA4 Channel 5 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mA5 Channel 6 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mA6 Channel 7 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mA7 Channel 8 0 = measurement range 0 – 20mA1 = measurement range 4 – 20mAData bit Designation Description7 – 15 reserved