7 Product-specific CAN objects XN300 slice modules7.20 XN-322-8AIO-U2262 Gateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu7.20.12 Input Channel x (Object 0x30B1 to 0x30B4)Objects 0x30B1 to 0x30B4 represent the formatted (integer) analog input val-ues.Design of the data bytes:7.20.13 Wire Break Diagnostic Messages (Object 0x30B5)Object 0x30B5 contains status information on the module's channels.Design of the data bytes:Byte 0:Sub-Index 1≦n≦254Feature Description / Value EDSName InputChannel1 Object 0x30B1 [MxSubExt30Bx]ParameterName=InputChannelxObjectType=0x7DataType=0x0003AccessType=roPDOMapping=1Count=1InputChannel2 Object 0x30B2InputChannel3 Object 0x30B3InputChannel4 Object 0x30B4Description Input Channel xObject Code ARRAYMapping PDOManualData type INTEGER16Sub index 01 … FE hexAccess ro1 Byte Byte 0:Sub index1≦n≦254B15B14B13B12B11B10B9B8B7B6B5B4B3B2B1B0MSBLSBFeature Description / Value EDSName Wire Break Detection [MxSubExt30B5]ParameterName=WireBreakDetectObjectType=0x7DataType=0x0006AccessType=roPDOMapping=1Count=1Description WireBreakDetectObject Code ARRAYMapping PDOManualData type UNSIGNED16Sub index 01 … FE hexAccess ro