7 Product-specific CAN objects XN300 slice modules7.15 XN-322-7AI-U2PT192 Gateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu7.15.9 Module Diagnostic Messages (Object 0x3080)Object 0x3080 contains status information on the module's general operat-ing status.Design of the data bytes:Byte 0:Sub-Index 1≦n≦254Byte 1:3 Byte Byte 2Sub index1≦n≦254B31B30B29B28B27B26B25B24B23B22B21B20B19B18B17B16MSBLSBFeature Description / Value EDSName ModuleDiag [MxSubExt3080]ParameterName=ModuleDiagObjectType=0x7DataType=0x0006AccessType=roPDOMapping=1Count=1Description Module Diagnostic MessagesObject Code ARRAYMapping PDOManualData type UNSIGNED16Sub index 01 … FE hexAccess roDefault value 0000 hex7 6 5 4 3 2 1 0– –Data bit Desig-nationMeaning Notes0 reserved1 0 = sync OK1 = no sync2 0 = OK1 = FLASH Data CRC Error-3 0 = OK1 =RAM Data CRC Error4 0 = OK1 = EEProm version not valid5-7 reserved