9 What Happens If …?Gateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu 3699 What Happens If …?If the XN-312-GW-CAN is not behaving as expected, the following tips mayhelp fix the problem. Only qualified persons should test electrical voltageswhile the device is in operation.Problem SolutionUnable to find the module underconfiguration in the EDS file.You are using an old EDS file version. Load and use the the current EDSfile, → Section “4.2 Project-specific EDS file”, page 50.LED ST flickers red/greenCommunication with gateway notpossible.The gateway is in the middle of detecting the CAN baud rate. Check thewiring of the CAN bus. Make sure that the CAN Master is connectedcorrectly. Set a fixed baud rate, → Section “1.5.2 Baud rate”, page 22.No transmission of analog values(Index 0x6401)Make sure that the analog values are enabled: Object Index 0x6423/Sub0=1 (AnalogInputGlobalInputEnable), → Section “7.15.3 AnalogInput Global Interrupt Enable (Object 0x6423)”, page 187Gateway with enabled monitoringboots continuouslyWith enabled analog values, make sure that the load of the CAN busdoesn't exceed 70%.• Use the filter settings for analog modules to reduce the bus load (seedescription of specific product)• The filter settings for DS-401: For the analog value 0x6401/Sub x thedelta values can be set at 0x6426/Sub x.• Use the possibility to provide a PDO with a sending delay (Inhibit-Time) or switch the PDOs transmission type to SYNCRON or RTR-only.CAN master indicates a guardingerror