1 XN-312-GW-CAN gateway1.5 Important data for engineering22 Gateway XN-312-GW-CAN 06/16 MN050003-EN www.eaton.eu1.5.2 Baud rateDIP switches 6 to 8 can be used to set a fixed baud rate for the gateway. IfDIP switches 6 to 8 are in the OFF position, the automatic baud rate detec-tion function, as described in CiA801, will be enabled. If the gateway is in themiddle of automatically detecting the baud rate, the ST LED will flash red/green and the gateway will adopt the field bus master's baud rate. Baudrates of 100 kBaud and 800 kBaud can only be set using automatic baud ratedetection, i.e., they cannot be set using the DIP switches.Cyclical CAN frames need to be sent on the field bus in order for the baudrate to be detected successfully. Otherwise, the gateway will not be able todetect the CAN baud rate.Figure 4: DIP switches for setting the baud rate→ If the device is unable to automatically determine the baud rate,use the DIP switches to set a fixed baud rate or add anotherCAN module to the system.fS1ONA 12345678910DDRRSTBOFFAuto detectionBaud rate [kBaud]10 20 50 125 250 500 10006 OFF ON OFF ON OFF ON OFF ON7 OFF OFF ON ON OFF OFF ON ON8 OFF OFF OFF OFF ON ON ON ON